Innovative power solutions.   Custom control systems.

North American Power & Controls, Inc.

Here’s a _HMB____ kW CAT emergency generator within a sound attenuated room designed built and maintained by NAPC.

Diesel Generator Preventative Maintenance Programs

Diesel Generator Routine Service

Diesel Generator Preventive Maintenance Program

 

We provide monthly, quarterly, annual service contracts for  standby and emergency generators throughout the San Francisco Bay Area. Our services are used by numerous private and public entities– let us give you a quote.

· Coolant and oil analysis to help determine the best time for replacement.   

· Load bank testing

· Filter and belt replacement.

· Control system simulation and testing.

· Governor tuning and load share calibration.

· Instrumentation calibration.

· Breaker testing and calibration.

· Report copies provided on site providing condition data and documenting any deficiencies.

Reliability built in.

Poor fuel quality and loss of prime disables many standby generators– we can provide customized fuel filter assemblies with built in priming pumps to both prevent an outage due to fuel condition, and allow easy fuel re-priming should a priming failure occur. This type of system is favored by hospitals, data centers, telecommunications sites.

 

Phone: 707-552-7318

Fax: 707-552-0551

E-mail: napcinc@pacbell.net

To contact us:

Text Box:

Reliability built in.

Jacket water heaters assist in providing quick reliable engine starting– here’s an installation showing a continuous duty canister type heater equipped with isolation valves (to allow replacement on line), silicone hi temp heater hose (to prevent premature heat cracking failure), circulating pump (to ensure that the entire block with remote radiator is heated), rubber shock mounts (to prevent vibration failure).